Data Sheet - iMOD112V047

Generate PDF

*Shown with optional CAN Monitoring Module

General

Part / Ordering Info:

iMOD112V047A23-01B Active Balancing, Digital OV, Analog Temperature

iMOD112V047A23-03B Active Balancing, CAN monitoring

iMOD112V047P23-01B Passive Balancing, Digital OV, Analog Temperature

iMOD112V047P23-03B Passive Balancing, CAN Monitoring

Cell_Base: 2000F

Electrical

Capacitance [NOM/MAX]: 47/50

Voltage: 113.4

DC ESR 10ms (mΩ) [Nom/Max]: 8.4/11.8

IEC DC ESR (mΩ) [Nom/Max]: 11.3/14.7

AC ESR (mΩ 1kHz) [Nom/Max]: 7.1/9.2

Hi Pot Test Voltage: 5000

UL Max Operational Voltage (per UL810A): 2000

Cycling (Calculated Values)

Continuous Current (A): TBD

Current Short Circuit (A): 13500

Current, Peak [1s] (A): 1900

Thermal (Reference)

Operational Storage Range: -40 to 85 °C

Resistance_Thermal (°C/W) [RTH]: TBD

Energy (Reference / Calculated using nominal values)

Emax (Whr) [Min/Nom]: 85.1/89.3

Height (mm): 224

Width (mm): 147

Length (mm): 798

Mass (kg): 33

Volume (L): 26

Terminal Fastener Size / Max Torque: M8/20Nm & M10/30Nm

Life (EOL Criteria) [CAP/ESR]

DC (10 Yr, 25°C, @VR): >36/<29

Endurance (2000hr, 85°C, @VR): >36/<29

Storage (2 yr, 70°C, @ 0V) >180/<4: >42/<22